在計算單臺發電機饋電的短路電流時,由于用等效電壓源cUn/ 代替同步發 電機的超瞬態電勢E〃,因此發電機的阻抗應用校正阻抗 。
電阻RG和超瞬態電抗X〃d的關系式可根據發電機額定電壓和視在功率按以下 范圍選用:
對UrG>1kV,SrG≥100MVA的發電機:RG=0.05X″d
對UrG>1kV,SrG<100MVA的發電機:RG=0.07X″d
對UrG≤1000V的發動機:RG=0.15 X″d
上一頁 [1] [2] [3] [4] [5] [6] [7] [8] [9] [10] [11] [12] [13] [14] [15] [16] [17] [18] [19] [20] [21] [22] [23] [24] [25] [26] [27] [28] [29] [30] [31] [32] [33] [34] [35] [36] [37] [38] [39] [40] [41] [42] [43] [44] [45] [46] [47] [48] [49] [50] [51] [52] [53] [54] [55] [56] [57] [58] [59] [60] [61] 下一頁 |